MIL-DTL-16036M(SH)
d. One frequency meter with transfer switch for reading frequency of generator and each bus tie frequency and
shore power for switchgear group containing shore power connection.
e.
One control switch for control of the generator circuit breaker.
f. Control switches as required (see 6.2) in conjunction with the governor speed regulation of the generator
prime mover.
g. One local/remote control transfer switch for the purpose of transferring control from the local station to the
EPCC. Monitoring and indicating circuits shall not be transferred except as noted below. Circuits transferred by
this switch shall include:
(1) Generator starting and stopping. Remote generator starting shall be transferred by the switch. Remote
generator stopping shall be locked out when the switch is in the local position. Local stopping and remote
emergency stopping shall be effective regardless of the position of the switch.
(2) Generator output voltage control.
(3) Prime mover governor manual control.
(4) Voltage regulator mode selection.
(5) Governor mode selection.
(6) Circuit breaker control of all circuit breakers which are controlled at the EPCC. This shall include
control of the synchronizing control system. Local automatic protection such as reverse power protection shall
remain operative regardless of the position of the local/remote transfer switch.
(7) Elements of the generator green light circuit which are duplicated locally and at the EPCC.
(8) Local/remote transfer switch position indication.
h.
Local/remote transfer switch position indicator light (white).
i. One control switch with indicator light (white) for control of the generator space heaters when provided
with the generator as specified (see 6.2).
j. Control switches, rheostats, and similar equipment that is designed for panel mounting and is required in
conjunction with the voltage regulator equipment mounted in the generator unit shall be mounted and operated from
the front panel as specified (see 6.2).
k. For installation in which a bus tie unit is not provided, one set of three ground indicator lights (clear) with a
control switch to indicate ground on the main bus or its connected feeders.
l. One synchroscope and one set of synchronizing lights (clear) with selector switch for synchronizing with
the main bus, the main bus with the bus tie circuit, and the bus tie with shore power switchgear group containing
shore power connection.
(1) For synchronizing monitor devices (Type I) and automatic paralleling devices (Type II):
(a) System selector switch for selecting the system to be paralleled. This switch may be combined
with the synchroscope selector switch.
(b) An indicator light (white) to indicate that the synchronizing control system is energized.
(2) For synchronizing monitor devices the following applies:
(a)
Synchronizing control monitor operating mode selector switch having Operating, Test, and Off
positions.
(3) For automatic paralleling devices the following applies:
(a)
One operating mode selector switch having Automatic, Manual Permissive, Test, and Off
positions.
(b) One pushbutton control switch for initiation of the automatic paralleling operation.
(c) An indicator light (red) to indicate that the synchronizing control equipment is unable to close the
circuit breaker when in the automatic mode.
(d) A pushbutton to interrupt the automatic paralleling cycle to completion of paralleling.
(e)
Indicating devices as required by MIL-S-24188.