MIL-DTL-16036M(SH)
bb. One reference switch for use in checking phase orientation of shore power connections. Two indicator
lights (green) to indicate phase orientation.
cc. One local/remote control transfer switch for the purpose of transferring control from the local station to the
EPCC. Monitoring and indicating circuits shall not be transferred except as noted below. This is required only on
ships provided with a centralized machinery control system including an EPCC when specified (see 6.2). Circuits
transferred by this switch shall include:
(1) Generator starting and stopping. Remote generator starting shall be transferred by the switch. Remote
generator stopping shall be locked out when the switch is in the local position. Local stopping and remote
emergency stopping shall be effective regardless of the position of the switch.
(2) Generator output voltage control.
(3) Prime mover governor manual control.
(4) Voltage regulator mode selection.
(5) Governor mode selection.
(6) Circuit breaker control of all circuit breakers which are controlled at the EPCC. This shall include
control of the synchronizing control system. Local automatic protection shall remain operative regardless of the
position of the local/remote transfer switch.
(7) Elements of the generator green light circuit which are duplicated locally and at the EPCC.
(8) Local/remote transfer switch position indication on the EPCC.
dd. One synchroscope and one set of synchronizing lights (clear) with selector switch for synchronizing with
the main bus, the main bus with the bus tie circuit, and the bus tie with shore power for switchgear group containing
shore power connection. Where the switchgear group has control of two generators and two bus tie circuits, the
synchroscope and synchronizing lights (clear) shall be connected for synchronizing either generator with the bus and
the bus with either bus tie circuit.
(1) For synchronizing monitor devices (Type I) and automatic paralleling devices (Type II):
(a) System selector switch for selecting the system to be paralleled. This switch may be combined
with the synchroscope selector switch.
(b) An indicator light (white) to indicate that the synchronizing control system is energized.
(2) For synchronizing monitor devices the following applies:
(a)
Synchronizing control monitor operating mode selector switch having Operating, Test, and Off
positions.
(3) For automatic paralleling devices the following applies:
(a)
One operating mode selector switch having Automatic, Manual Permissive, Test, and Off
positions.
(b) One pushbutton control switch for initiation of the automatic paralleling operation.
(c) An indicator light (red) to indicate that the synchronizing control equipment is unable to close the
circuit breaker when in the automatic mode.
(d) A pushbutton to interrupt the automatic paralleling cycle to completion of paralleling.
(e)
Indicating devices as required by MIL-S-24188.
3.4.1.5.4 Submarine EPCP. The following shall be mounted on submarine EPCPs:
For each ship s service turbine generator: items (a), (b), (e), (j), (m), (p), (q), and (z) of 3.4.1.5.3.
a.
b. For each ship s service motor generator: items (a), (b), (m), and (p) of 3.4.1.5.3 and the following
additional devices:
(1) Control switches, rheostats, and similar devices as required (see 6.2) in conjunction with speed
regulating equipment.
(2) One control switch with indicator light (blue) for control of each motor circuit breaker.
(3) One ammeter, zero center scale, for reading DC current.
17