MIL-DTL-16036M(SH)
l. One remote control switch or other remote control devices as required, and indicator light (white) to control
the speed governor on the remote generator prime mover where the unit has control of a remote generator. Control
power shall be connected through the transfer switch, item (k), of the remote EPCP, and the indicating light shall be
energized when the transfer of control to the remote station is accomplished.
m. One control switch with circuit breaker closed indicator light (blue) for control of each local generator
circuit breaker.
n. One control switch with circuit breaker closed indicator light (blue) for control of each bus tie circuit
breaker.
o. One control switch with circuit breaker closed indicator light (blue) for control of each electrically-operated
distribution circuit breaker.
p. One control switch with space heater on indicator light (white) for control of generator space heater (when
provided with the generator) for each local generator when specified (see 6.2).
q. Test receptacle with test plugs for connecting portable instruments to the metering current and potential
circuits. Removal of the receptacle protective cover shall automatically short circuit the secondary of metering
current transformers, so that only the meters are electrically removed from the secondary circuit.
r. One transfer switch with two indicator lights (white) for connecting the switchboard control bus to the local
450-volt ship s service bus, or the 450-volt emergency supply. The transfer may be accomplished automatically;
however, in such cases one source of power shall be the local 450-volt ship s service bus and the second source shall
be a 450-volt bus tie supply.
s.
One set of three ground indicator lights (clear) with a test switch to indicate ground conditions on the main
bus.
t. Dead-front fuse panel for fusing the control circuits. Dead-front fuseholders shall be of the type listed in
3.14.2.1 in accordance with MIL-PRF-19207.
u. One mimic bus system (dark type) simulating the generator and bus tie connections shall be provided and
shall consist of the following:
(1) Indicator lights (white) for each generator to indicate generator running and voltage available.
(2) Indicator lights (yellow) for each generator and bus tie circuit breaker.
(3) Single-pole, double-throw switches shall be provided for each circuit breaker light. These switches
shall be combined with their respective yellow lights and so arranged that when the switch handle indication and the
circuit breaker position (open or closed) are the same, the light shall be out. When the circuit breaker position and
the switch handle indication are different, the light shall be lit. For indicator light power supply, see 3.11.7.
(4) Mimic bus material shall be 1/8 inch thick, 1/4 inch, 3/4 inch, or 1/2 inch wide, as specified (see 6.2).
Mimic bus material shall be laminated plastic conforming to Grades ES-1, ES-2, or ES-3 of ASTM D709; aluminum
alloy conforming to ASTM B209, alloy 5052; commercial brass conforming to ASTM B36/B36M and
ASTM B121/B121M; corrosion resisting steel conforming to Type 316 of ASTM A167, ASTM A240/A240M, and
ASTM A666; or nickel-copper alloy conforming to ASTM B127, ASTM B164, and ASTM B564.
v.
One ammeter to indicate current in the bus tie.
w. One ammeter for each remote generator for reading one phase of generator current.
x. One shore power circuit breaker control switch for each shore power station to simultaneously operate all
circuit breakers for that station. One indicator light (blue) for each shore power circuit breaker to indicate breaker
closed. One indicator light (white) per shore power receptacle to indicate the shore power feeder energized. One
indicator light (white) to indicate the bus feeder energized. These indicator lights shall be mounted near the shore
power circuit breaker control switch.
y. One control switch with one blue and one white indicator light for each electrically-operated circuit breaker
feeding an emergency switchboard.
z.
One ammeter for reading the shore power current.
aa. One switchboard type phase sequence indicator with a multiposition selector switch, for use in checking
phase rotation and orientation of shore power connections.
16
For Parts Inquires submit RFQ to Parts Hangar, Inc.
© Copyright 2015 Integrated Publishing, Inc.
A Service Disabled Veteran Owned Small Business