MIL-DTL-16036M(SH)
c.
For a diesel generator:
(1) Control switches, rheostats, and similar equipment that are for panel mounting, and as required in
conjunction with the voltage regulator equipment mounted in the generator unit, shall be mounted on and operated
from the EPCP (see 6.2).
(2) One control switch with indicator light (blue) for control of the diesel generator circuit breaker.
(3) One AC ammeter for reading one phase of the generator current.
(4) One polyphase wattmeter for reading the generator power output.
(5) One control switch or other control devices as required, for control of the governor on the generator
prime mover as specified (see 6.2).
d.
For the battery:
(1) Two zero center scale DC ammeters, one high range and one low range, to measure battery charge and
discharge currents.
(2) One battery float charge measuring device.
(3) One hydrogen detector remote indicator.
(4) One control switch with indicator light (blue) for control of each battery circuit breaker.
(5) One battery exhaust fan control switch with indicator light (green).
(6) One battery ventilation flow indicator.
(7) One control switch with ammeter to control and indicate operation of battery recirculating fans.
e.
For the system:
(1) One synchroscope with synchronizing selector switch for synchronizing generators with the bus and
the bus with bus tie circuits.
(2) Two frequency meters and two voltmeters connected through the synchronizing selector switch for
reading frequency and voltage on each side of the point at which synchronizing is being performed.
(3) One DC voltmeter with selector switch for reading battery and DC bus voltages.
(4) One transfer switch with two indicator lights (white) for connecting the AC control bus to a 450-volt
normal and alternate source of supply.
(5) One transfer switch with two indicator lights (white) for connecting the DC control bus to a normal and
alternate DC supply.
(6) A direct reading ground detector.
(7) Dead-front fuse panel for fusing control circuit. Dead-front fuseholders shall be of the type listed in
3.14.2.1 in accordance with MIL-PRF-19207.
(8) One mimic bus system simulating the generators, bus ties, shore power, and battery connections of the
power system [see 3.4.1.5.3(u)].
(9) A transfer device with indicator light (white) shall be installed for supplying each DC control bus from
either its respective motor generator DC bus or from the battery side of the battery circuit breaker.
(10) Test receptacles with test plugs shall be provided for connecting portable instruments to all metering
and potential circuits on the EPCP. Removal of the receptacle protective cover shall automatically short circuit the
secondaries of the metering current transformers so that only the meters are electrically removed from the secondary
circuit.
3.4.1.5.5 400 Hertz EPCP for solid-state frequency changer systems. The following shall be mounted on the
400 Hertz EPCP:
a. One mimic bus system (dark type) simulating the frequency changer and bus tie connections shall be
provided and shall consist of the following:
(1) Indicator lights (white) for each frequency changer to indicate frequency changer energized and
voltage available.