MIL-DTL-16036M(SH)
NATIONAL ELECTRICAL MANUFACTURERS ASSOCIATION (NEMA)
NEMA HP 6
-
Electrical and Electronic Silicone and Silicone Braided Insulated, Hook-Up Wire,
Types S (600 V), ZHS (600 V), SS (1000 V), ZHSS (1000 V), and SSB Braided
(1000 V)
(Copies of this document are available from the National Electrical Manufacturers Association, 1300 North 17th
Street, Suite 1847, Rosslyn, VA 22209 or online at www.nema.org.)
SAE INTERNATIONAL
SAE-AS7928
-
Terminals, Lug: Splices, Conductor: Crimp Style, Copper, General Specification For
(Copies of this document are available from SAE World Headquarters, 400 Commonwealth Drive, Warrendale, PA
15096-0001 or online at www.sae.org.)
SOCIETY FOR PROTECTIVE COATINGS (SSPC)
SSPC SP 2
-
Hand Tool Cleaning
SSPC SP 3
-
Power Tool Cleaning
(Copies of these documents are available from SSPC Publication Sales, 40 24th Street, 6th Floor, Pittsburgh, PA
15222-4656 or online at www.sspc.org.)
2.4 Order of precedence. Unless otherwise noted herein or in the contract, in the event of a conflict between
the text of this document and the references cited herein, the text of this document takes precedence. Nothing in this
document, however, supersedes applicable laws and regulations unless a specific exemption has been obtained.
3. REQUIREMENTS
3.1 First article. When specified (see 6.2), a sample shall be subjected to first article inspection in accordance
with 4.2.
3.2 General requirements.
3.2.1 Safety. The switchgear shall provide fail-safe features for safety of personnel during the installation,
operation, maintenance, and repair or interchanging of a complete equipment assembly or component parts thereof.
Equipment design for personnel safety shall be equal to or better than the appropriate requirements of the
Occupational Safety and Health Act (OSHA) as identified in Title 29, Part 1910, of the Code of Federal Regulations
(CFR). Except as required herein, safety shall be in accordance with MIL-E-917.
3.2.2 Accidental contact. The switchgear shall provide protection to personnel against accidental contact with
voltages in excess of 30 volts root mean square (RMS) or DC with all removable panels in place and hinged doors
closed.
3.2.3 Design life. All switchboards and switchboard equipment that are detailed in this specification shall have
a minimum design life of not less than 30 years. Specific components not meeting this requirement shall be
identified.
3.3 Detailed requirements.
3.3.1 Materials, parts, and process. Except as required herein, materials, parts, and processes (such as, but not
limited to, prohibited materials, metals or coatings, threaded parts and fastening devices, electrical insulation,
soldering, and brazing) shall be in accordance with MIL-E-917. When a requirement of MIL-E-917 conflicts with a
requirement of this specification, the requirements of this specification shall govern.
3.3.1.1 Switchgear groups. Whether or not specifically mentioned for the various units, switchgear groups
shall be complete with all devices required to accomplish the function specified hereinafter.
3.3.1.2 Cadmium. Elemental cadmium shall not be present in any component of the final product.
7