MIL-DTL-2212K(SH)
TABLE VI. Hp rating for AC contactors and controllers. (see 6.2)
Rating of polyphase single-speed, full-voltage magnetic controllers for nonplugging
and nonjogging duty
Continuous
3-phase hp at
rating
Size of controller
115 V
440 V
(amperes)
0
18
2
5
1
27
3
10
2
45
7½
25
3
90
15
50
4
135
30
100
5
270
---
200
6
540
---
400
7
810
---
600
Ratings of polyphase reduced-voltage, general purpose, reversing or nonreversing
(see 6.8.49) magnetic controllers
Continuous
3-phase hp at
Size of controller
rating
115 V
440 V
(amperes)
1
27
3
10
2
45
7½
25
3
90
15
50
4
135
30
100
5
270
---
200
6
540
---
400
7
810
---
600
Ratings for wye-delta magnetic controllers for nonreversing, nonjogging duty for
open or closed-circuit transition (see 6.8.102)
Continuous rating
Size of controller
3-phase hp at 440 V
(amperes)
1
47
15
2
78
40
3
156
75
4
233
150
5
467
300
6
935
700
7
1400
1000
21