MIL-DTL-2212K(SH)
d.
Switches: (see 6.2)
Type: Manual
Automatic
Push-button
Pressure
Rotary selector
Thermostatic
Drum (see 6.8.88)
Limit
Float (see 6.8.89)
Proximity
Photoelectric
Function: Usually to actuate a magnetic controller
Location: Local
Remote
3.16.15 Horsepower (hp) ratings. Controllers shall be provided in the sizes, and shall conform to the applicable
TABLE V. Hp rating for DC contactors and controllers. (see 6.2)
Hp ratings of reduced-voltage magnetic controllers
Continuous
rating
115 V hp
230 V hp rating
Size of controller
(see 6.8.60)
rating
(250 V nom)
(amperes)
1
25
3
5
2
50
5
10
3
100
10
25
4
150
20
40
5
300
40
75
6
600
75
150
7
900
110
225
Hp rating of full-voltage magnetic controllers
Continuous
Hp at
rating
Size of controller
115 V
230 V
(amperes)
0
15
1
1
1
25
1½
2
20