MIL-PRF-17773C(SH)
TABLE VIII. Qualification tests and conformance inspections. Continued.
Requirement
Qualification Test
Conformance Inspection
Tests
Paragraph
Radiated Susceptibility, Magnetic
and Electric Fields, Spikes and
--
Power Frequencies
Power
--
Chassis Leakage Current
--
Protection
Compatibility with Active Ground
--
Fault Detector Circuit
Endurance and Overload
--
Short-Circuit Withstandability
--
Dielectric Withstanding Voltage
--
Degree of Enclosure
--
Ambient Temperature
--
Humidity
--
Pressure
--
Temperature Rise
--
Inclined Operation
--
Shock
--
Vibration
--
Airborne Noise
--
Structureborne Noise
--
4.5 Examination. Each switch shall be examined for compliance with the requirements specified in Table VIII.
This element of inspection shall encompass all visual examinations and dimensional measurements. The
examination shall be conducted using the classifications of defects as specified in Table IX as applicable.
Noncompliance with any specified requirements or presence of one or more defects preventing or lessening
maximum efficiency shall constitute cause for rejection.
TABLE IX. Classification of defects.
Related Requirements
Categories
Defects
Paragraph
001
Prohibited materials are used.
002
Insulating material not as specified or not provided as required.
003
Supply line and load terminal markings not as specified.
004
Manual operation for ABT switch not provided as required.
005
Preferred source selector switch not provided as specified.
Time delay circuits not provided as specified or instantaneous is not
006
within maximum time limit specified.
18