MIL-DTL-16036M(SH)
3.14.1 Fusing of transformers. Each metering potential transformer shall be fused on the primary side with a
separate fuse in each leg of each transformer. Fuse size shall be 250 to 400 percent of transformer rated primary
current. Control transformers shall be fused on the primary side. Transformer secondary circuits shall not be fused,
except where a circuit leaves the switchboard. In such a case, the ungrounded portion of the circuit which leaves the
switchboard shall be fused, and the fuses shall be located so as not to open any other circuits on the local
switchboard. One 6-ampere fuse shall be provided in each primary leg of each indicator light transformer. The
control circuits for electric operation of circuit breakers shall be fused for short circuit protection only. Potential
circuits for generator voltage regulators on excitation systems shall not be fused.
3.14.2 Fuse mounting. Fuses mounted on switchboards shall be accessibly located for replacement. Fuses shall
be grouped on subpanels and the length of leads between fuses and the power circuit taps shall be kept to a
minimum.