MIL-DTL-16036M(SH)
TABLE XI. Classification of defects Continued.
Classification
Defects
Major:
122
Evidence that bus bar supports not spaced in accordance with short circuit current available, high-
impact shock and vibration requirements.
123
Evidence that bus bar capacity nonconforming.
124
Cable connectors not of specified type; solder, if authorized, not as specified.
125
Means not provided for connecting cables from other units or sections; cable connection
arrangement restricts access.
126
Instrument and control wiring nonconforming; not connected as specified; not grouped and
strapped as specified.
127
Terminal boards not provided where required.
128
Synchronizing circuits, where required, not connected in specified manner; synchronizing control
equipment not as specified.
129
Indicator lights, space heater circuits, transformers, voltage regulators, and trip circuits for ACB
circuit breakers not connected or arranged in accordance with applicable specifications or
drawings.
130
Wiring not marked or tagged.
131
Circuit breakers not of type specified; location and mounting nonconforming; drawout mechanism
(for Type ACB only) not operable as specified.
132
Switches not in accordance with specification; instrument control switches not type or not marked
as specified; handle not required shape.
133
Disconnect devices not of specified type; not mounted as required; tools, if required, not located
properly.
134
Fuses not in accordance with specification; location identifications and mounting nonconforming.
135
Fuseholders, where required, not enclosed or not in accordance with drawing.
136
Terminal boards exceed allowable length.
137
Instruments not in accordance with specification; case, scale, and mounting nonconforming.
138
Transformers not in accordance with applicable specifications; not provided; not connected as
specified; not protected where required.
139
Relays not as specified; not accepted type.
140
Indicator lights nonconforming; not color required by code; resistors not as specified; lamps not
provided.
141
Rear and top enclosures not secured firmly to frame; will not clear live bus work if buckled; top
flanges do not prevent water from seeping into the enclosure; panel fastening not as specified
method employed for making thumbscrews captive inadequate.
142
Top enclosure shape, form, and flanges nonconforming; corners not welded watertight.
143
Buses not marked to indicate polarity or phase.
144
Devices, where so required by applicable specification, not qualified for listing on Qualified
Products Lists (QPLs).
Minor:
201
Painting procedure specified not followed; primer not applied as specified; enamel not of
specified type.