MIL-DTL-29183/1B
TABLE II. Connector assignment and connector terminal wiring.
Phase
Neutral
Ground,
Phase
Phase
green
C,
,
A,
B,
Circuit
Function
Interface connectorą
white
(bare)
red
blue
black
wire
wire
wire
wire
wire
Input, 208V,
NEMA L21-30P
X
Y
Z
W
G
1
3-phase
Branch, 120V,
2, 3
NEMA L5-20R
X
-
-
W
G
1-phase
Branch, 120V,
NEMA L5-20R
-
X
-
W
G
4, 5
1-phase
Branch, 208V,
6
NEMA L14-20R
-
X
Y
W
G
1-phase
Branch, 208V,
NEMA L14-20R
X
-
Y
W
G
7
1-phase
Feedthrough
NEMA L21-30R
X
Y
Z
W
G
8
208V, 3-phase
1
Connector designations are National Electrical Manufacturers Association (NEMA) type numbers.
See MIL-DTL-29183.
Custodian:
Preparing Activity:
Navy - YD
DLA - GS2
(Project 6110-0443-001)
Review Activity:
Navy - MC
5
For Parts Inquires submit RFQ to Parts Hangar, Inc.
© Copyright 2015 Integrated Publishing, Inc.
A Service Disabled Veteran Owned Small Business