MIL-DTL-29183C
4.5.7 Stacking test. Three distribution panels of the same type, class, and configuration
shall be stacked, one placed on top of the other, without the use of any intervening load
distributing material. The distribution panels and covers shall show no evidence of damage as
specified in 3.8.5.1.
4.5.8 Type II and sound level test. The distribution panelboard sound level for type II
only shall be tested as specified in NEMA ST 20, except that the distribution panel shall be
considered as the noise source instead of the transformer, and, where applicable, all
measurements shall be made relative to the distribution panel instead of the transformer. The
sound level shall conform to 3.8.10.2.
5. PACKAGING
5.1 Packaging. For acquisition purposes, the packaging requirements shall be as specified
in the contract or order (see 6.2). When actual packaging of material is to be performed by DoD
personnel, these personnel need to contact the responsible packaging activity to ascertain
requisite packaging requirements. Packaging requirements are maintained by the inventory
control point's packaging activity within the military department or defense agency, or within the
military department's system command. Packaging data retrieval is available from the managing
military department's or defense agency's automated packaging files, CD-ROM products, or by
contacting the responsible packaging activity.
6. NOTES
(This section contains information of a general or explanatory nature that may be helpful,
but is not mandatory.)
6.1 Intended use. The distribution panels are used for the distribution of electrical power.
Class 1 distribution panels are intended for 3-phase power, while class 2 panels are intended for
single-phase power. Type I distribution panels do not incorporate a transformer, while type II
panels include a transformer for voltage conversion. The configuration of the distribution panel is
as specified by the applicable specification sheet.
6.2 Acquisition requirements. Acquisition documents should specify the following:
a. Title, number, and date of this specification.
b. Type, class, and configuration of panel required (see 1.2).
c. Issue of DODISS to be cited in the solicitation, and if required, the specific issue of
individual documents referenced (see 2.2.1 and 2.3).
d. Title, number, and date of the applicable specification sheet (see 3.1).
e. When a first article is required for inspection and approval, and the time schedule
imposed for such submission (see 3.3 and 4.2).
f. When hex wrenches are required to be furnished (see 3.8.7).
g. Treatment and paint option, to include camouflage pattern and type, if applicable (see 3.11).
h. If certification in lieu of test is not applicable (see 3.12).
i. Packaging requirements (see 5.1).