Stability: The vertical center of gravity shall be not more than 21.0 inches (533 mm)
above level ground. Additional stability requirements shall apply in
accordance with MIL-DTL-29183.
Electrical:
Input: The input to the distribution panel shall be 208Y/120 volt (V) or 208 V, 3-phase
(ø), 4-pole (P), 5-wire (W), 60 Hertz (Hz).
Bus capacity: The bus bar capacities shall be 800 amperes (A) (see figure 1).
Provision for modification: Design provisions shall be made to accommodate the
future installation of an additional 3P-350A main breaker
and an additional set of input terminals for dual input
capability.
Circuit breaker: The number of poles and current rating shall be as indicated in table
herein and the voltage rating shall be sufficient for the intended circuit.
PIN: The government part identification number (PIN) is as follows:
M 29183 / 6
Specification sheet number
General specification number
Prefix