MIL-DTL-29183/4C
TABLE I. Circuit characteristics.
Circuit breaker
Interface connectorą
Quantity
Circuit kind
Pole (P) - Ampere (A)
1
480V, 3-phase, 5W
3P-225A
Terminals
1
480V, 3-phase, 4W
3P-225A
Terminals
3
480V, 3-phase, 4W
3P-100A
Terminals
1
480V, 3-phase, 3W
3P-20A
Terminals
1
208Y/120V, 3-phase, 5W
3P-100A
Terminals
2
208Y/120V, 3-phase, 4W
2P-50A
Terminals
2
208Y/120V, 3-phase, 5W
3P-30A
NEMA L21-30Rą
14
120V, 1-phase, 3W
1P-20A
NEMA L5-20Rą
1
Connector designations are National Electrical Manufacturers Association (NEMA) type numbers.
See MIL-DTL-29183.
TABLE II. Connector assignment and connector terminal wiring.
Ground,
Phase
Phase
Phase
Neutral,
green
B,
C,
A,
white
Circuit
Function
Interface connector
(bare)
blue
black
red
wire
wire
wire
wire
wire
Pressure type,
Input, 480V,
T1
T2
T3
T0
G
1
terminal block,
3-phase
minimum 250
Output, 480V,
kcmilą wire size
L1
L2
L3
-
G
2
3-phase
capacity
Pressure type,
Branch, 480V,
A
B
C
-
G
3, 4, 6
terminal block,
3-phase
minimum No. 1
Paralleling,
AWG˛ wire size
P1
P2
P3
P0
G
3P
480V, 3-phase
capacity
Pressure type,
Branch or
terminal block,
5
alternate input,
minimum No. 1
X
Y
Z
W
G
208V, 3-phase
AWG˛ wire size
capacity
4