MIL-DTL-29183/4C
Stability: The vertical center of gravity shall be not more than 17.0 inches (432 mm)
above level ground. Additional stability requirements shall apply in
accordance with MIL-DTL-29183.
Electrical:
Input: The input to the distribution panel shall be 480 volt (V) or 208 V, 3-phase (ø),
4-pole (P), 5-wire (W), 60 Hertz (Hz).
Bus capacity: The bus bar capacities shall be 400 amperes (A) and 200 A
(see figure 1).
Transformer: The transformer shall be 3-phase, 15 kilovolt-ampere (kva), dry type
with a primary to secondary voltage of 480 to 208 V. Three 5 kva
1-phase transformers may be used in place of a single 3-phase
transformer. The transformer(s) shall use a delta to wye (primary to
secondary) configuration. The neutral of the transformer secondary
shall be connected to the neutral bus bar as indicated in figure 1.
Circuit breaker: The number of poles and current rating shall be as indicated in table I
herein and the voltage rating shall be sufficient for the intended circuit.
PIN: The government part identification number (PIN) is as follows:
M 29183 /4
Specification sheet number
General specification number
Prefix
2
For Parts Inquires submit RFQ to Parts Hangar, Inc.
© Copyright 2015 Integrated Publishing, Inc.
A Service Disabled Veteran Owned Small Business