MIL-DTL-29183/2B
Stability:
The vertical center of gravity shall be not more than 11.0 inches (280 mm)
above level ground. Additional stability requirements shall apply in
accordance with MIL-DTL-29183.
Lifting attachments: Crane lifting attachments are not required (see MIL-DTL-29183).
A carrying handle is required.
Electrical:
Input: The input to the distribution panel shall be 208Y/120 volt (V), 3-phase (ø),
4-pole (P), 5-wire (W), 60 Hertz (Hz).
Bus capacity: The bus bar capacity shall be 100 amperes (A).
Provision for modification: Design provisions shall be made to accommodate the future
installation of an additional 3P-60A main breaker and an
additional MS90558C32412P connector for dual input
capability.
Circuit breaker: The number of poles and current rating shall be as indicated in table I
herein and the voltage rating shall be sufficient for the intended circuit.
PIN: The government part identification number (PIN) is as follows:
M 29183 /2
Specification sheet number
General specification number
Prefix