MIL-DTL-29183/17A
TABLE I. Circuit characteristics.
Circuit breaker
Interface connector
Quantity
Circuit kind
Pole (P) - Ampere (A)
208Y/120V,
3P-100A
MS90558C44412P¹
1
3-phase, 5W
208Y/120V,
4
3P-60A
MS90555C32412S¹
3-phase, 5W
208Y/120V,
3P-30A
MS90555C32412S¹
2
3-phase, 5W
208Y/120V,
2
3P-40A
MS90555C32412S¹
3-phase, 5W
120V,
1P-20A
NEMA L5-20R²
3
1-phase, 3W
¹ Connector designations are military part numbers for military type connectors conforming to MIL-C-22992.
See MIL-DTL-29183.
² Connector designations are National Electrical Manufacturers Association (NEMA).
TABLE II. Connector assignment and connector terminal wiring.
Ground,
Phase
Phase
Phase
C,
Neutral,
green
A,
B,
Circuit
Function
Interface connector
(bare)
blue
white
black
red
wire
wire
wire
wire
wire
G1, G2
1
Input
MS90558C44412P¹
A
B
C
N
G3, G4
3, 4, 5, 6
Branch
MS90555C32412S¹
A
B
C
N
G
7, 8, 9, 10
Branch
MS90555C32412S¹
A
B
C
N
G
11
Branch
L5-20R²
X³
W
G
12
Branch
L5-20R²
X³
W
G
13
Branch
L5-20R²
X³
W
G
¹
Connector designations are military part numbers for military type connectors conforming to MIL-C-22992.
See MIL-DTL-29183.
² Connector designations are National Electrical Manufacturers Association (NEMA).
³ Unmarked terminal.