MIL-DTL-29183/17A
Electrical:
Input: The input to the distribution panel shall be 208Y/120 volt (V), 3-phase (ø),
4-pole (P), 5-wire (W), 60 Hertz (Hz).
Bus capacity: The bus bar capacities shall be 225 amperes (A) (see figure 1).
Circuit breaker: The number of poles and current rating shall be as indicated in table I
herein and the voltage rating shall be sufficient for the intended circuit.
Modification capability: Design provisions shall be made to accommodate in the future
an additional 3P-400A main breaker and a knockout for 100A,
class L in put connection (MS90558C44412P).
PIN: The government part identification number (PIN) is as follows:
M 29183 / 17
Specification sheet number
General specification number
Prefix
2
For Parts Inquires submit RFQ to Parts Hangar, Inc.
© Copyright 2015 Integrated Publishing, Inc.
A Service Disabled Veteran Owned Small Business