MIL-DTL-29183/5C
TABLE I. Circuit characteristics.
Circuit breaker
Interface connectorą
Quantity
Circuit kind
Pole (P) - Ampere (A)
1
480V, 3-phase, 5W
3P-225A
Terminals
1
480V, 3-phase, 4W
3P-225A
Terminals
3
480V, 3-phase, 4W
3P-100A
Terminals
1
480V, 3-phase, 3W
3P-40A
Transformer
1
208Y/120V, 3-phase, 5W
3P-100A
Terminals
2
208Y/120V,1-phase, 4W
2P-50A
Terminals
4
208Y/120V,3-phase, 5W
3P-30A
NEMA L21-30Rą
8
120V,1-phase, 3W
1P-20A
NEMA L5-20Rą
1
Connector designations are National Electrical Manufacturers Association (NEMA) type numbers.
See MIL-DTL-29183.
TABLE II. Connector assignment and connector terminal wiring.
Ground,
Phase
Neutral
Phase
Phase
,
green
B,
C,
A,
Circuit
Function
Interface connector
white
(bare)
red
blue
black
wire
wire
wire
wire
wire
Pressure type,
Input, 480V,
1
T1
T2
T3
T0
G
terminal block,
3-phase
minimum 250
Output, 480V, kcmilą wire size
2
L1
L2
L3
-
G
3-phase
capacity
Pressure type,
Branch,
3, 4, 6
A
B
C
-
G
480V, 3-phase terminal block,
minimum No. 1
Paralleling,
AWG˛ wire size
3P
P1
P2
P3
P0
G
480V, 3-phase capacity
4