MIL-DTL-29183/3B
TABLE I. Circuit characteristics.
Circuit breaker
Interface connectorą
Quantity
Circuit kind
Pole (P) - Ampere (A)
1
208Y/120V, 3-phase, 4P, 5W
3P-100A
MS90558C44412P
4
208Y/120V, 3-phase, 4P, 5W
3P-60A
MS90555C32412S
2
208Y/120V, 3-phase, 4P, 5W
3P-40A
MS90555C28412S
2
208Y/120V, 3-phase, 4P, 5W
3P-20A
MS17346R24N10S
1P-20A,
MS17346R22N2S
2
120V, 1-phase, 2P, 3W
GFCI type
1
Connector designations are military type connectors conforming to MIL-C-22992. See MIL-DTL-29183.
TABLE II. Connector assignment and connector terminal wiring.
Neutral
Ground,
Phase
Phase
Phase
,
green
B,
C,
A,
Circuit
Function
Interface connectorą
(bare)
blue
white
black
red
wire
wire
wire
wire
wire
G1, G2
1
Input
MS90558C44412P
A
B
C
N
G3, G4
3, 4, 5, 6
Branch
MS90555C32412S
A
B
C
N
G
7,8
Branch
MS90555C28412S
A
B
C
N
G
9, 10
Branch
MS17346R24N10S
F
B
E
A
C
11
Branch
MS17346R22N2S
B
-
-
C
A
12
Branch
MS17346R22N2S
-
B
-
C
A
1
Connector designations are military type connectors conforming to MIL-C-22992. See MIL-DTL-29183.