MIL-DTL-29183/19A
Electrical:
Input: The input to the distribution panel shall be 208Y/120 volt (V), 3-phase (ø),
4-pole (P), 5-wire (W), 60 Hertz (Hz).
Bus capacity: The bus bar capacities shall be 800 amperes (A) (see figure 1).
Circuit breaker: The number of poles and current rating shall be as indicated in table I
herein and the voltage rating shall be sufficient for the intended circuit.
An interlock bar shall be provided between the two main breakers to
preclude both breakers from being in the "on" position at the same
time. Interlocking of circuit breakers shall be accomplished through a
mechanical interlock. Interlocking shall be of the break before make
type; of two interlocked circuits, one cannot be made (circuit closed or
energized) until the other is first broken (circuit open or de-energized).
Interlocking between the first circuit breaker and the second circuit
breaker shall be provided to preclude the first circuit breaker from
being closed when the second circuit breaker is closed, and to preclude
the second circuit breaker from being closed when the first circuit
breaker closed.
PIN: The government part identification number (PIN) is as follows:
M 29183 / 19
Specification sheet number
General specification number
Prefix
2
For Parts Inquires submit RFQ to Parts Hangar, Inc.