MIL-DTL-29183/18A
TABLE I. Circuit characteristics.
Circuit breaker
Interface connector
Quantity
Circuit kind
Pole (P) - Ampere (A)
208Y/120V,
3P-400A
Terminals
2
3-phase, 5W
(Non-automatic)
208Y/120V,
6
3P-100A
MS90555C44412S¹
3-phase, 5W
208Y/120V,
3P-60A
MS90555C32412S¹
6
3-phase, 5W
¹ Connector designations are military part numbers for military type connectors conforming to MIL-C-22992.
See MIL-DTL-29183.
TABLE II. Connector assignment and connector terminal wiring.
Ground,
Phase
Phase
Phase
Neutral,
green
B,
C,
A,
Circuit
Function
Interface connector
(bare)
blue
white
black
red
wire
wire
wire
wire
wire
Pressure type,
1
Input
T1
T2
T3
T0
G
terminal dual lugs,
4/0 AWG to
2
Input
P1
P2
P3
P0
G
300 kcmil²
G1, G2,
3, 4, 5,
Branch
MS90555C44412S¹
A
B
C
N
6, 7, 8
G3, G4
9, 10, 11,
Branch
MS90555C32412S¹
A
B
C
N
G
12, 13, 14
¹
Connector designations are military part numbers for military type connectors conforming to MIL-C-22992.
See MIL-DTL-29183.
² 1000 (k) circular (c) mils (mil).
4
For Parts Inquires submit RFQ to Parts Hangar, Inc.
© Copyright 2015 Integrated Publishing, Inc.
A Service Disabled Veteran Owned Small Business